Installation of welded-on pieces in pipelines and their use for pressure sensing

Pressure sensing area:
Turbine gas meters: from 6 DN before the gas meter to 5 DN
Rotary gas meters: from 2 DN in front of the gas meter to 4 DN

 

Use of welded-on pieces:
A, B - connection of an indicating pressure gauge
C, D - connection of a registration pressure gauge,
gas quantity counters, pressure sensors, etc.

jnsinst1

Connecting the registration pressure gauge in the same room or within a 5m length of impulse pipe ( D ):

  • extension NTP 20, on which is screwed the shut-off valve for pressure gauges ČSN 13 7517.5 type A 
    (type B) through a pressure gauge socket adapter (part of the shut-off valve to the pressure gauges), PM 20L/8 screw connection
  • tube f 8mm ČSN 42 6711.31 of the appropriate length
  • screw the PM 20P/8 fitting onto the registration pressure gauge

Connection of the registration pressure gauge outside the room or above 5 m of impulse pipe length ( C ):

  • extension NTP 20, on which the shut-off valve for pressure gauges ČSN 13 7517.5 type A is screwed
    (type B) through a pressure gauge socket adapter (part of the shut-off valve to the pressure gauges), PM 20L/8 screw connection
  • tube f 8mm ČSN 42 6711.31 of the appropriate length
  • screw fitting PM 20P/8, shut-off valve for pressure gauges ČSN 13 7517.5 type A (type B) screw on
    to the registration pressure gauge via the pressure gauge socket adapter (part of the closing valve to the pressure gauges)

Installation of direct welded-on pieces in a horizontal pipe for temperature sensing

jnsinst2

Note 1:
welded-on piece NPVM 20.1 + threaded plug ZZM 20.0
welded-on piece NPVM 27.1 + threaded plug ZZM 27.0
welded-on piece NPVG 34.1 + threaded plug ZZG 34.0

Note 2:
welded-on piece NPVM 27.1 + thermometer well TJS M + technical thermometer - 30 to + 50 °C

Note 3:
NPVM 20.1 welded-on piece + PJS recalculator well
NPVM 27.1 welded-on piece + PRJS M recalculator well
NPVG 34.1 welded-on piece + PRJS G counter well
NPVM 27.1 welded-on piece + RJS register thermometer well
 NPVM 20.1 welded-on piece + TJSP sensor well

The lengths of the "C" welded-on pieces used correspond to the nominal diameter DN and the size of the well used, see table 1:jnsinst3

 

DN (mm) Welded-on piece Length C (mm) Well Plug
50 NPVM 20 30 - ZZM 20
NPVM 20 50 - ZZM 20
NPVM 27 35 - ZZM 27
NPVM 27 50 TJS M100 ZZM 27
NPVM 27 70 TJS M100, TJS M125 ZZM 27
NPVG 34 35 - ZZG 34
NPVG 34 50 TJS G100 ZZG 34
NPVG 34 70 TJS G100, TJS G125 ZZG 34
80 NPVM 20 30 - ZZM 20
NPVM 20 50 PJS 01, PJS 02 ZZM 20
NPVM 27 35 TJS M100 ZZM 27
NPVM 27 50 TJS M100, TJS M125, PRJS M03 ZZM 27
NPVM 27 70 TJS M125, RJS 125, PRJS M03, PRJS M04 ZZM 27
NPVG 34 35 TJS G100 ZZG 34
NPVG 34 50 TJS G100, TJS G125, PRJS G01 ZZG 34
NPVG 34 70 TJS G125, PRJS G01, PRJS G02 ZZG 34
100 NPVM 20 30 PJS 01 ZZM 20
NPVM 20 50 PJS 01, PJS 02, TJSP 160 ZZM 20
NPVM 27 35 TJS M100, TJS M125, PRJS M03 ZZM 27
NPVM 27 50 TJS M100, TJS M125, RJS 125, PRJS M03, PRJS M04 ZZM 27
NPVM 27 70 TJS M125, TJS M160, RJS 125, PRJS M03, PRJS M04 ZZM 27
NPVG 34 35 TJS G100, TJS G125, PRJS M03 ZZG 34
NPVG 34 50 TJS G100, TJS G125, PRJS G01, PRJS G02 ZZG 34
NPVG 34 70 TJS G125, TJS G160, PRJS G01, PRJS G02 ZZG 34
150 NPVM 20 30 PJS 01, PJS 02, TJSP 160 ZZM 20
NPVM 20 50 PJS 01, PJS 02, TJSP 160 ZZM 20
NPVM 27 35 TJS M100 až TJS M160, RJS 125, RJS 160, PRJS M03, 04 ZZM 27
NPVM 27 50 TJS M100 až TJS M160, RJS 125, RJS 160, PRJS M03, 04 ZZM 27
NPVM 27 70 TJS M125, TJS M160, RJS 125 až RJS 200, PRJS M03, 04 ZZM 27
NPVG 34 35 TJS G100 až TJS G160, PRJS G01, PRJS G02 ZZG 34
NPVG 34 50 TJS G100 až TJS G160, PRJS G01, PRJS G02 ZZG 34
NPVG 34 70 TJS G125, TJS G160, PRJS G01, PRJS G02 ZZG 34

In the case of installation of oblique welds in a horizontal pipeline, the wells must face against the direction of gas flow! Table 2 applies to this case (see below)

Installation of scarf welded-on piecses in a vertical pipe for temperature sensing

jnsinst4

Note 1:
welded-on piece NSM 20.1 + threaded plug ZZM 20.0
welded-on piece NSM 27.1 + threaded plug ZZM 27.0
welded-on piece NSG 34.1 + threaded plug ZZG 34.0

Note 2:
welded-on piece NSM 27.1 + thermometer well TJS M
+ technical thermometer - 30 to + 50 °C

Note 3:
welded-on piece NSM 20.1 + PJS counter sump
welded-on piece NSM 27.1 + PRJS M recalculator sink
welded-on piece NSG 34.1  + PRJS G counter sump
welded-on piece NSM 27.1 + RJS registration thermometer well
welded-on piece NSM 20.1 + TJSP sensor well

The lengths of the "C" welded-on pieces used correspond to the nominal diameter DN and the size of the well used, see table 2:

jnsinst5

DN (mm) Welded-on piece Length C (mm) Well Plug
50 NSM 20 25 - ZZM 20
NSM 20 50 PJS 01, PJS 02, ZZM 20
NSM 27 35 TJS M100 ZZM 27
NSM 27 50 TJS M125 ZZM 27
NSM 27 70 RJS 125 ZZM 27
NSG 34 35 TJS G100 ZZG 34
NSG 34 50 TJS G125 ZZG 34
NSG 34 70 ZZG 34
80 NSM 20 25 PJS 01, PJS 02 ZZM 20
NSM 20 50 PJS 01, PJS 02, TJSP 160 ZZM 20
NSM 27 35 TJS M100, TJS M125, PRJS M03, PRJS M04 ZZM 27
NSM 27 50 TJS M125, TJS M160, RJS 125, PRJS M03, PRJS M04 ZZM 27
NSM 27 70 TJS M160, RJS 125, RJS 160, PRJS M03, PRJS M04 ZZM 27
NSG 34 35 TJS G100, TJS G125, PRJS G01, PRJS G02 ZZG 34
NSG 34 50 TJS G125, TJS G160, PRJS G01, PRJS G02 ZZG 34
NSG 34 70 TJS G160, PRJS G01, PRJS G02 ZZG 34
100 NSM 20 25 PJS 01, PJS 02, TJSP 160 ZZM 20
NSM 20 50 PJS 01, PJS 02, TJSP 160 ZZM 20
NSM 27 35 TJS M100 až TJS M160, RJS 125, PRJS M03, PRJS M04 ZZM 27
NSM 27 50 TJS M125, TJS M160, RJS 125, RJS 160, PRJS M03, PRJS M04 ZZM 27
NSM 27 70 TJS M160, RJS 125, RJS 160, PRJS M04 ZZM 27
NSG 34 35 TJS G100 až TJS G160, PRJS G01, PRJS G02 ZZG 34
NSG 34 50 TJS G125, TJS G160, PRJS G01, PRJS G02 ZZG 34
NSG 34 70 TJS G160, PRJS G02 ZZG 34
150 NSM 20 25 PJS 01, PJS 02, TJSP 160, TJSP 250 ZZM 20
NSM 20 50 PJS 01, PJS 02, TJSP 160, TJSP 250 ZZM 20
NSM 27 35 TJS M100 až TJS M160, RJS 125 až RJS 200, PRJS M03, PRJS M04 ZZM 27
NSM 27 50 TJS M125, TJS M160, RJS 125 až RJS 200, PRJS M03, PRJS M04 ZZM 27
NSM 27 70 TJS M160, RJS 160 až RJS 200, PRJS M04 ZZM 27
NSG 34 35 TJS G100 až TJS G160, PRJS G01, PRJS G02 ZZG 34
NSG 34 50 TJS G125, TJS G160, PRJS G01, PRJS G02 ZZG 34
NSG 34 70 TJS G160, PRJS G02 ZZG 34

EXAMPLE OF USING A BUILDING SYSTEM FROM THIN-WALLED PROFILES FOR MOUNTING GAS QUANTITY CONVERTERS (Elcor-94), DATA LOGGERS (Datcom), PRESSURE SENSORS, ETC.

jnsinst6jnsinst6